The unit in the device of execution 3 works as a FACIE
with the possibility of expanding the functions of the fire control device when
the SCB block and other devices are connected by shielded two-wire information
line.
The
unit in the device of execution 4 works as a FACIE and ensures:
- receiving reports of fire and malfunction
detectors included in the thirty-two loops;
- ensures the issuance of a command by
shielded two-wire information line for manual and automatic start of fire
fighting, with the help of the unit SCB;
- ensures the issuance of a command by
shielded two-wire information line for the termination, restoration and
discharging of the start, with the help of the unit SCB;
- reception on the controlled duplex
information line of information signals from the blocks "ALTO 2000
BCP";
- formation of alarms, malfunctions,
disabling of ventilation;
- the inclusion of warning blocks
("FIRE!");
- light and sound indication of operating
modes.
-
Intended
use
The scope of application consists in protection of
industrial objects premises, banks, warehouses, underground and aboveground
garages, tunnels, residential and administrative buildings, as well as other
objects, on which, the conditions of blocks usage are constructive.
Functional features of the block:
- reception of messages from detectors
connected directly to the loops of signaling (number of alarm loops is up
to 32);
- the issuance of a fire alarm signal to the
operator by light and sound signals indicating the number of the loop and
filling in the alarm in the event log, issuing a fire alarm signal by
closing the relay contact;
- issuing of a signal error to the light and
sound signals operator indicating the number of the loop and filling in
the failures in the event log, the issuance of a fault signal by closing
the relay contact;
- the formation of the ventilation disabling
signal in the automatic mode while the operation of two loops of the
alarm, or when the manual start is activated;
- the light-control signal alert
- formation of a command for launching the
SCB units, if the "AFFS" mode is allowed, the “Automatic mode”
mode is automatically operated in two separate plugs of the block
corresponding to one direction of fire extinguishing;
- formation of a command for manual start of
SCB blocks in the manual and automatic fire extinguishing modes - by the
operator command from the control panel of the block (by pressing the
button of the corresponding zone under the cover, which bends);
- provides the issuance of an information
command for the SCB blocks for the stop and restart startup by the
operator from the control panel of the block by pressing the button
"ON/OFF" on the shielded two-wire information line;
- provides an indication of the cease-start
(LED "Delay Start");
- provides the issuance of an information
team for the SCB blocks to the start disable of the SCB by the operator
from the control panel of the block by pressing the "RESET"
button on the shielded two-wire information line;
- the display of transmission, reception,
confirmation of start-up from the corresponding SCB on the indicators of
the control panel of the block;
- filling in the nonvolatile log of messages
about all events and operator actions;
- automatic switch to standby power supply
with indication of the power supply mode on the control panel;
- manual testing of indication bodies in the
"CHECK" mode.